以下是一个示例的shell脚本,它使用snmp协议获取UPS设备性能指标,并将它们输出为Prometheus Metrics标准格式。
#!/bin/bash
# Define the OID values for the UPS metrics we want to retrieve
UPS_OID=".1.3.6.1.2.1.33"
UPS_INPUT_FREQUENCY_OID="$UPS_OID.3.1.3"
UPS_OUTPUT_VOLTAGE_OID="$UPS_OID.4.1.2"
UPS_BATTERY_RUNTIME_REMAINING_OID="$UPS_OID.2.3.1"
UPS_LOAD_PERCENTAGE_OID="$UPS_OID.4.1.5"
# Retrieve the UPS metrics using snmpwalk command and parse the output
ups_input_frequency=$(snmpwalk -v 2c -c public localhost $UPS_INPUT_FREQUENCY_OID | awk '{print $NF}')
ups_output_voltage=$(snmpwalk -v 2c -c public localhost $UPS_OUTPUT_VOLTAGE_OID | awk '{print $NF}')
ups_battery_runtime_remaining=$(snmpwalk -v 2c -c public localhost $UPS_BATTERY_RUNTIME_REMAINING_OID | awk '{print $NF}')
ups_load_percentage=$(snmpwalk -v 2c -c public localhost $UPS_LOAD_PERCENTAGE_OID | awk '{print $NF}')
# Output the UPS metrics in Prometheus Metrics format
echo "ups_input_frequency{hostname=\"$(hostname)\"} ${ups_input_frequency}"
echo "ups_output_voltage{hostname=\"$(hostname)\"} ${ups_output_voltage}"
echo "ups_battery_runtime_remaining{hostname=\"$(hostname)\"} ${ups_battery_runtime_remaining}"
echo "ups_load_percentage{hostname=\"$(hostname)\"} ${ups_load_percentage}"
该脚本首先定义了要检索的OID值。然后,它使用snmpwalk命令检索UPS指标,并使用awk命令从输出中提取每个度量值。最后,它将每个度量值输出为Prometheus Metrics格式,其中包括主机名和度量值。
要运行此脚本,请确保您的系统上已安装snmpwalk命令,并且已经配置了UPS设备以通过SNMP协议公开这些指标。在终端中输入以下命令即可运行脚本:
bash ups_metrics.sh
如果一切正常,您将看到类似以下内容的输出:
ups_input_frequency{hostname="yourhostname"} 59.8
ups_output_voltage{hostname="yourhostname"} 119.2
ups_battery_runtime_remaining{hostname="yourhostname"} 1200
ups_load_percentage{hostname="yourhostname"} 50